Data Centres - UKS North

500 4kW racks in 930m2 space available from June

If you would like to speak to us about this new Tier-4 datacentre space, please contact us via our on-line enquiry form or call us on 0845 004 1333. A detailed specification is published below.

The facility has been designed and built to offer high specification hosting using the very latest energy saving technologies and equipment. Where possible it uses fresh air, rather than refrigeration, to extract the heat from the cooling circuits which run through the data floors. The lack of windows to suites reduces solar gain, and increases security.

You can see the progress of the build which commenced 22nd October 2007 and is due to complete it's final tests in June 2008.
First Generator in position Core & Shell data floor

Core & Shell data floor


 

 

Downloads

 

PDF Download the UKS North datasheet for facility details

Enquire here or call 0845 004 1333

 

 

Building Specification

Technical (hosting) Space 930 sq metres (10,000 sq feet) arranged as 500 foot-prints
Floor Loading 5kN per square metre
Building Layout Technical space split over two floors
Other Amenities Site security office
Heavy duty service lift
Linkway to UKS South at high and low level
Meeting room and other offices
Provisions for extended on-site working Customer rest area equipped with welfare amenities
Customer toilets and showers


Power Specification

Power Specification 2.5kW/M2 per system, A+B systems for resiliency
Utility supply 3.8MVA 11kV site supply delivered via dual cable arrangement
Core Distribution 2 x 2MVA Transformers feeding A and B supplies
Backup UPS Two independant systems per floor comprising of 5 x 200KVA units per system to provide true diverse feeds and protect customer equipment during transfer to generators
Generators 2 x 1MVA prime rated diesel generator systems at launch, upto 5 parallel (4+1 spare) in line with load requirements.
Generator Autonomy 115,000 litres fuel (1 week) with fuel supply agreements
Power per Footprint Suites designed to average 4kW per footprint

Environmental Specification

Cooling - Specification 2.5kW/M2 load (resiliency through per system, A+B systems
22±2 degrees celsius
Cooling - Air Handling 12 x 42kW net air handling units per suite arranged in A+B systems at 100% capacity per system into pressurised floor
Cooling - Chillers and Redundancy 2 x 300kW energy efficient "dry coolers" with ambi-cool technology per suite arranged in A+B systems at 100% capacity per system.
Monitoring Suite based centrally managed Building Management System, with monitoring including: temperature; leak detection; occupancy; sound levels; and BMS input from air-handing units, fire systems and other local M&E equipment.
Lighting Occupancy based lighting with minimum lighting "always on".
No external windows to suites.
Fire Detection Building wide fire detection with suite based multi-zones with both ionisation and optical detectors in roof, data floor and raised floor VESDA aspirating smoke detectors
Fire Suppression FM-200® Heptafluoropropane compatible agent
Access Site perimeter control with "pod" style anti-tailgating man trap doors between building reception and secure areas
Site Security 24x7 On-site security
PAC access control system with audit logs and formal documented site access policy
Internal and external CCTV with 90 days of motion activated capture

Other Network Provision

Roof Space Apparatus for satellite and radio equipment subject to planning
On-site Fibre Providers via UKS South BT (Stratford, Ipsley & Redditch Headless Cross exchanges), Virgin Media [ntl & Telewest connections] (Studley, Bromsgrove & Kings Norton exchanges) Deliveries via independent ducts from public highway
Telecommunications Access BT and ntl:Telewest (Fibre, Copper and SDH), Global Crossing (Fibernet) via Birmingham, Telehouse East or Sovereign House POPs, Interconnect to Carriers present in Telecity Sovereign House and Telehouse East via UKS POP's